ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.2.1.1(e) Car Lighting
|
|
|
Emergency lights shall work.
|
9/5/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Provide max counterweight sign in the pit.
|
9/5/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
8/28/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
The emergency power jewel/indicator shall be operational to indicate unit has transferred to emergency power. Emergency power shall be tested and the emergency power jewel shall be operational.
|
11/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power operation not working. Generator would not transfer power.
|
7/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
7/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
The in car emergency light shall be operational.
|
7/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.4 Means for Manual Release
|
x
|
|
The manual brake release was not able to be tested. Testing procedures shall be kept on-site.
|
7/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
x
|
|
Fire stops are missing on both hoistway doors at 1st and 2nd floors.
|
7/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
7/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
x
|
2-way communication device shall work. Red Tag Issued, phone did not work on 7/5/23 inspection.
|
8/21/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.4 Means for Manual Release
|
x
|
|
Emergency brake release handle shall work.
|
8/21/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current state operating permit shall be obtained and displayed in the equipment room.
|
8/21/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.4 Means for Manual Release
|
x
|
|
Emergency brake release handle shall work. Violation still remains as of 8/21/24.
|
10/25/2024
|
conversion
|
conversion
|
n/a
|
|
|
Car emergency lighting shall work.
|
9/5/2019
|