Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. 5/10/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve. Due to the installation year of 2011, a category 5 test shall be performed on the overspeed valve on or before the next annual inspection. This is no record of a category 5 test, if such record exists, please provide. 5/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers Pit sump cover is not flush to floor and does not cover hole completely. 5/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit shall be kept dry. Remove severe rust from pit equipment, repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak. Remove dehumidifier. 5/20/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 5/20/2024