Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) x Pit stop switch and housing are damaged. Repair and re-test.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 Electrical box in pit area is pulled from wall and damaged. Wiring is exposed. Repair as needed.
ASME A18.1-2005 : Lifts & Chairlifts 2.11 - Emergency Signals 2.11.2 x The emergency phone shall be operational. 8/4/2023
ASME A18.1-2005 : Lifts & Chairlifts 2.11 - Emergency Signals 2.11.2 x The emergency phone shall be operational (2nd Notice). 10/12/2023
ASME A18.1-2005 : Lifts & Chairlifts 2.11 - Emergency Signals 2.11.2 x Phone must be able to reach live person by pushing the call button. Note: Once the call button is pressed, the call is picked up by an automated operator asking for the person to press 1 or 2, which is not an option from the lift. 11/7/2023
ASME A18.1-2005 : Lifts & Chairlifts 2.11 - Emergency Signals 2.11.2 x 2-way communication device shall work and be answered 24/7. Phone calls out, goes straight to voicemail.
ASME A18.1-2005 : Lifts & Chairlifts 2.6 - Platforms 2.6.6.3 Auxiliary Lighting (Re-Inspection) x Emergency lighting shall work. Test button is broken, location of lighting breaker is unknown.