Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) A Maintenance Control Program for each unit shall be provided by the person(s) and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times 7/27/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary Power fails to bring the car down and open the doors when normal power is removed. 2/13/2024
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. 5/17/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Car top "Up" inspection button is not functioning. Car only operates in the down direction while on car top inspection.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) Missing Bottom Hoistway Door Safety Retainers. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail 7/27/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The Emergency Light does not work when normal power is removed 11/11/2025