Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Yes No Auxiliary Power fails to bring the car down and open the doors when normal power is removed. 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) No No Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail 7/27/2022
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 No No Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. 5/17/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Auxiliary Power fails to bring the car down and open the doors when normal power is removed. Indicates a drained battery. 2/21/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No The Emergency Light does not work when normal power is removed 2/23/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Auxiliary Power fails to bring the car down and open the doors when normal power is removed. 5/7/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6 7/27/2022