ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
Repair inoperative door restrictor. 7 day reinspection required. Unit will be red-tagged in not repaired.
|
8/16/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Need a maintenance control program on site and posted on controller
|
11/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
11/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5.1 Examination and Maintenance of Packing Glands and Seals
|
x
|
|
The packing on both jacks are leaking, need to be replaced. Re-inspection required
|
7/19/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.5 - Traveling cables
|
8.11.3.1.5(f)
|
|
|
Traveling cables are cracked, needs to be replaced. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
1/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.14 - Ventilation
|
2.14.2.3
|
x
|
|
Elevator cab ventilation fan does not work on auxiliary power (battery backup), needs repaired. Re-inspection required
|
10/4/2024
|
conversion
|
conversion
|
n/a
|
|
|
Packing on both jacks leaking, pit needs to be cleaned
|
11/23/2020
|
conversion
|
conversion
|
n/a
|
|
|
Car sill is approx .1 inch above car floor, tripping hazard
|
11/23/2020
|
conversion
|
conversion
|
n/a
|
|
|
Door restrictor must be operational
|
11/23/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
x
|
|
Cylinder head on hydraulic jack has leaking packing seal, need to replace seal. Re-inspection required
|
7/16/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Elevator cab emergency lights do not work, need repaired. Re-inspection required
|
7/16/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Elevator cab phone does not work, needs repair. Re-inspection required
|
12/8/2022
|