Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Car sill is approx .1 inch above car floor, tripping hazard 11/23/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance x Cylinder head on hydraulic jack has leaking packing seal, need to replace seal. Re-inspection required 7/16/2024
conversion conversion n/a Door restrictor must be operational 11/23/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Elevator cab emergency lights do not work, need repaired. Re-inspection required 7/16/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Elevator cab phone does not work, needs repair. Re-inspection required 12/8/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 2.14.2.3 x Elevator cab ventilation fan does not work on auxiliary power (battery backup), needs repaired. Re-inspection required 10/4/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Re-inspection required 1/11/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Need a maintenance control program on site and posted on controller 11/23/2020
conversion conversion n/a Packing on both jacks leaking, pit needs to be cleaned 11/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 11/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x Repair inoperative door restrictor. 7 day reinspection required. Unit will be red-tagged in not repaired. 8/16/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.1 Examination and Maintenance of Packing Glands and Seals x The packing on both jacks are leaking, need to be replaced. Re-inspection required 7/19/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.5 - Traveling cables 8.11.3.1.5(f) Traveling cables are cracked, needs to be replaced. Re-inspection required