MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work, needs repair. Re-inspection required
|
11/4/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.14 - Ventilation
|
2.14.2.3
|
x
|
|
Elevator cab ventilation fan does not work on auxiliary power (battery backup) needs repaired. Re-inspection required
|
10/4/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Need a maintenance control program on site posted on controller
|
11/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.11 - Plunger and Cylinder
|
3.18
|
x
|
|
The synchronization cables on both telescoping hydraulic jack plungers are showing signs of broken wires and deterioration. Replace synchronization cables, also replace missing synchroninization cable guard. Re-inspection required
|
10/4/2024
|
conversion
|
conversion
|
n/a
|
|
|
Door restrictor must be operational
|
11/23/2020
|
conversion
|
conversion
|
n/a
|
|
|
Packing on bith jacks leaking pit needs to be cleaned
|
11/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
11/23/2020
|