                        MO Minimum : Elevators
                     | 
                    
                        (B) - Car Enclosure: Passenger
                     | 
                    
                        (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Phone in elevator cab does not work, needs repair. Re-inspection required
                     | 
                    
                        11/4/2022
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.14 - Ventilation
                     | 
                    
                        2.14.2.3
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Elevator cab ventilation fan does not work on auxiliary power (battery backup) needs repaired. Re-inspection required
                     | 
                    
                        10/4/2024
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        2.41 - Maintenance Records
                     | 
                    
                        8.6.1.4
                     | 
                    
                     | 
                    
                     | 
                    
                        Need a maintenance control program on site posted on controller
                     | 
                    
                        11/23/2020
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        5.11 - Plunger and Cylinder
                     | 
                    
                        3.18
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The synchronization cables on both telescoping hydraulic jack plungers are showing signs of broken wires and deterioration. Replace synchronization cables, also replace missing synchroninization cable guard. Re-inspection required
                     | 
                    
                        10/4/2024
                     | 
                
                
                    | 
                        conversion
                     | 
                    
                        conversion
                     | 
                    
                        n/a
                     | 
                    
                     | 
                    
                     | 
                    
                        Door restrictor must be operational
                     | 
                    
                        11/23/2020
                     | 
                
                
                    | 
                        conversion
                     | 
                    
                        conversion
                     | 
                    
                        n/a
                     | 
                    
                     | 
                    
                     | 
                    
                        Packing on bith jacks leaking pit needs to be cleaned
                     | 
                    
                        11/23/2020
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        CSR 40-5.100 State Operating Certificate
                     | 
                    
                        5.100(2) Display of Operating Certificate
                     | 
                    
                     | 
                    
                     | 
                    
                        Post current state certificate in machine room
                     | 
                    
                        11/23/2020
                     |