Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Phone in elevator cab does not work, needs repair. Re-inspection required 11/4/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.14 - Ventilation 2.14.2.3 Yes No Elevator cab ventilation fan does not work on auxiliary power (battery backup) needs repaired. Re-inspection required 10/4/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 Yes No The synchronization cables on both telescoping hydraulic jack plungers are showing signs of broken wires and deterioration. Replace synchronization cables, also replace missing synchroninization cable guard. Re-inspection required 10/4/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 11/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Need a maintenance control program on site posted on controller 11/23/2020
conversion conversion n/a No No Door restrictor must be operational 11/23/2020
conversion conversion n/a No No Packing on bith jacks leaking pit needs to be cleaned 11/23/2020