Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x The auxiliary power lowering operation shall be functional. An uninterruptible power supply for the emergency lowering operation was sitting on the floor of the machine room. When an elevator is equipped with this device, it has to be operational and can't be removed without the permission of the MO AHJ. 7/22/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x The following violation cited in 2023 has not been corrected: The auxiliary power lowering operation shall be functional. An uninterruptible power supply for the emergency lowering operation was sitting on the floor of the machine room. When an elevator is equipped with this device, it has to be operational and can't be removed without the permission of the MO AHJ. Note: This has auxiliary power unit has not yet been re-installed. See MO Memorandum 016 for more information regarding this violation. 1/10/2025