Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide an MCP in machine room to log maintenance, repairs, and inspections.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices x x smoke detectors were not ready to test 10/21/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures x the phase 2 instruction sign on the car operating panel does not match the operation now that the elevator has been modernized 10/21/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.11.2.1.4(b) x bend down the fire tabs on all gibs on all floors 10/21/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) x patch all penetrations in wall between hoistway and machine room 10/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Unit not operational at this time needing parts 1/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x bell and light working phone does not work 4/18/2024