ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
bell and light working phone does not work
|
4/18/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.11.2.1.4(b)
|
x
|
|
bend down the fire tabs on all gibs on all floors
|
10/21/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
8.11.2.1.3(p)
|
x
|
|
patch all penetrations in wall between hoistway and machine room
|
10/21/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide an MCP in machine room to log maintenance, repairs, and inspections.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices
|
x
|
x
|
smoke detectors were not ready to test
|
10/21/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters' Emergency Operation: Operating Procedures
|
x
|
|
the phase 2 instruction sign on the car operating panel does not match the operation now that the elevator has been modernized
|
10/21/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Unit not operational at this time needing parts
|