Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Ffs stop switch not working correctly. Once used doesn't allow door operation after returning to run. Must key off phase 2 to return to main floor to reset. Doors work again. 5/21/2025
MO Minimum : Elevators (H) - Machine Rooms (H)8 Electrical boxes and wiring from recent work needs to be cleaned up. Covers need to be installed
MO Minimum : Elevators (H) - Machine Rooms (H)8 Electrical boxes and wiring from recent work needs cleaned up. Covers on.