Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Emergency lights shall work 12/9/2019
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) x Suspension ropes are undersized and rouged, need to be replaced. Re-inspection required 2/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Smoke guard barrier on floor 3 is rolled up and on top of enclosure. Barrier shall be repaired so that it will work in case of emergency. 2/25/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The “smoke guard” barrier device, that was installed on a number of hoistway door landings, has been activated and not reset properly. The device has been temporarily wrapped up rendering it inoperable in case of an actual emergency. Repair and reset all “smoke guard” barrier devices to operate as designed. 2/3/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Smoke guard barrier on floor 3 is rolled up and on top of enclosure. Barrier shall be repaired so that it will work in case of emergency.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.16 - Traveling cables and junction boxes 2.8.1 The car traveling cable, underneath the car, is cracked through the outer insulation as the car reaches the lobby. Confirm that no internal wires have been affected and repair or replace traveling cable. 2/3/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Elevator is not transferring to generator power when the generator transfer switch is activated. Repair and reinspect. 2/25/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. 2/3/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The emergency power testing, door pressure, and unintended motion test before the inspection is completed. 2/3/2026