ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone dies not operate.
|
9/9/2019
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No maintenance control plan on site
|
10/19/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
No maintenance records on site
|
10/19/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No MCP
|
11/2/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
No maintenance records on site.
|
11/2/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
post emergency evacuation of passengers form inside machine
|
3/15/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Remove rags and oil cans from machine floor.
|
3/15/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
8.6.3
|
x
|
|
SUSPENSION ROPES NEED REPLACED. ENLARGED ROPES WOULD NO GO INTO GO / NO GO GUAGE
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys (Re-Inspection)
|
x
|
|
provide firefighter key on site or inside machine room.
|
4/12/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters' Emergency Operation: Operating Procedures
|
|
|
post firefighter instructions adjacent to the hall fire keyswitch.
|
3/15/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current state operating certificate not displayed in control room
|
10/19/2022
|