Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A maintenance log shall be kept on-site. 3/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing A monthly fire service test log shall be kept on-site. 3/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.39 - Low Oil Protection 3.26.9 Low Oil Protection (Re-Inspection) x The low pressure switch shall be tested. 12/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing x The overspeed valve is due for a category 5 test. The overspeed valve shall be sealed and tagged after a successful category 5 test. 12/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing The overspeed valve shall be scheduled for a category 5 test with the rated load on or before the next annual inspection. 4/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. Not operational as of 2/9/23. 4/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. 2/9/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. 12/22/2022