A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13
|
|
|
Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail.
|
5/17/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency Phone in car fails to establish two-way communication. No dial tone.
|
2/22/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.11.2.1.1(o)
|
|
|
Provide Phase I Fire Fighters Operation Instructions at first floor hall station
|
7/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.11.2.1.3(w)
|
|
|
Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail
|
7/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6
|
7/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency Light doesn't work when on backup power
|
7/25/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
x
|
|
Auxiliary Power fails to bring the car down and open the doors when normal power is removed. Indicates a low battery.
|
|