Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. 5/17/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication. No dial tone. 2/22/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) Provide Phase I Fire Fighters Operation Instructions at first floor hall station 7/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail 7/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6 7/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency Light doesn't work when on backup power 7/25/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x Auxiliary Power fails to bring the car down and open the doors when normal power is removed. Indicates a low battery.