Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x standby power illumination signals not working 6/11/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt displayed 6/15/2023
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(t) couldnt run a ascending car test 7/15/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(b)(5) need testing procedures for unintended motion an ascending car on site 6/24/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(c)(3) phone testing proceedures not on site 6/24/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 incorrect test proceedures for the equipment on site 7/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emg. phone not working emg. lt not working 6/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emg. lt not working 7/14/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x unable to test emg power at time of insp 6/20/2024