Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair the emergency phone as the incoming line is dead
A17.1-1996 : Elevators 3.2 - Car top light and outlet 204.7 Provide a guard on the car top light.
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x Replace all the suspension ropes as they are too short. there is not sufficent tail length beyond the shackel for proper finishing. and far to much distance between the buffer and the car counterweight. Over 3 feet. 9/28/2023
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 202 Replace the bad guide wheels on the counterweight right side.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room.