Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) The governor rope shall be tagged as specified by CSR 40-5.065(L)1. 1/17/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) The suspension ropes shall be tagged as specified by CSR 40-5.065(L)1. 1/17/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits The pit shall be kept dry. 10/26/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits There is a pipe on the front pit wall discharging water into the pit. The pipe shall be removed or sealed. 10/26/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.20 Suspension rope tail ends shall be properly seized/banded. Electrical tape is not proper. 1/17/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a current MO state operating certificate in the elevator machine room. 3/12/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 3/2/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) The receptacle in the machine room shall be a GFCI. 10/26/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.22 - Wire rope fastening and hitch plate 8.11.2.1.3(bb) x The suspension rope clip shall be properly spaced. 3/2/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.22 - Wire rope fastening and hitch plate 8.11.2.1.3(bb) x The suspension rope clip shall be properly spaced. 10/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.11.2.1.4(b) x The hoistway doors are missing the middle hanger. 10/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.11.2.1.4(b) x The hoistway doors are missing the middle fire gib. 10/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.11.2.1.4(b) x The hoistway doors are missing the middle hanger. 3/2/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.11.2.1.4(b) x The hoistway doors are missing the middle fire gib. 3/2/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) x The counterweight runby shall not exceed 6.5 inches. 3/2/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/26/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code compliant MCP including onsite documents. 3/12/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Note: 2022 & 2023 records are blank. 1/17/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The wood in the control room shall be removed or painted with an intumescent paint. 10/26/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 8.6.1.6.3 Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. There are no schematics on-site. 1/17/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The governor rope shall be tagged as specified by CSR 40-5.065(L)1. 1/17/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The suspension ropes shall be tagged as specified by CSR 40-5.065(L)1. 1/17/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.11.1 Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. There are no schematics on-site. 1/17/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 x The counterweight runby shall not exceed 6.5 inches. 10/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x The in car emergency lighting shall be operational. 2/11/2020