Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) Clean oil from pit floor 1/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide a code data plate conforming to sec 8.9 12/20/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Provide maintenance control plan on site posted on controller 1/25/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair phone in car 2/26/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 Seismic (Earthquake protection) 8.4.10 This elevator has a rupture valve and is overdue for testing. Last test was at acceptance in 2012. 7/23/2020