Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (F) - Electrical Switches (F)9 Disconnect shall be lockable. 6/14/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements A variance is required to allow a residential elevator to remain active in a public building. 6/14/2019
MO Minimum : Elevators (I) - Pits (I)3 Warning chains shall be attached to the bottom the counterweights. 6/14/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) A pit light shall be provided. 7/10/2022
MO Minimum : Elevators (I) - Pits (I)7 A stop switch shall be provided in the pit. 7/10/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Performed as much of the annual inspection as possible. Special tools are needed to set the safeties and complete the test. The safeties shall be tested to complete the annual inspection. 12/30/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 7/10/2022