Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. 6/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. Second Notice 3/2/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.27 - Crosshead data plate 2.16.3 x A cross head data plate shall be provided. 3/8/2021
MO Minimum : Elevators (I) - Pits (I)1 x There is an unknown pipe protruding from the pit floor. The pipe shall be removed or a variance applied for. 3/8/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 x Label the disconnects with the location, source, and breaker numbers of the panel from which it is fed. 3/8/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing x A monthly fire service testing log shall be provided. 3/8/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 x All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 3/8/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall operate properly. 3/8/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate x A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 3/8/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2018 4/30/2021
MO Minimum : Elevators (A) - Hoistways (A)13 The elevator hoistway shall be fully enclosed. Inside the hoistway drywall has become dislodged due to flooding that shall be repaired and the elevator shaft shall retain its hoistway fire rating. 4/30/2021
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 The belts on the hydraulic pump motor are cracked and worn unevenly. Replace belts for a smooth operation of pump to motor. 4/30/2021