A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(j)
|
|
|
machine room fire extinguisher does not have an inspection tag
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the copy of the state operating certificate posted in the machine room is to be updated annually
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
the alarm bell did not work on normal power or an battery power
|
10/19/2021
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(j)
|
|
|
machine room fire extinguisher does not have an inspection tag
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
the alarm bell did not work on battery power or on 110 volt power
|
11/7/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.2.1.5(a)
|
|
|
the pit light bulb was burnt out, replace light bulb
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.2.1.1(e) Car Lighting
|
|
|
replace emergecy light battery, the lights did not come on when the 110v lights were turned off
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Perform monthly fire service test and post test log in the machine room
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
alarm bell did not work on normal power or on emergency power
|
10/30/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
the machine room fire extinguisher does not have and inspection tag
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
alarm bell did not work on battery power or on normal power, replace emergency battery
|
11/3/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work
|
11/3/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
machine room state operating certificate is from 2014, update with new copy when received from the state annually
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
machine room fire extinguisher does not have inspection tag
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone did not work
|
1/21/2025
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell did not work on battery power or on building power
|
1/21/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
x
|
Repair the emergency phone.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate on display in the machine room expired in 2014, update annually with the current state operating certificate when received from the state
|
|