Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 2.21 top right hand counterweight slide guide insert is missing, replace insert
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate machine room state operating certificate is from 2019, update with new copy when received from the state annually
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate on display in the machine room expired 2019, update annually with the current state operating certificate when received from the state
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the copy of the state operating certificate posted in the machine room is to be updated annually
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(j) machine room fire extinguisher did not have an inspection tag
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(j) the machine room fire extinguisher does not have an inspection tag
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 machine room fire extinguisher does not have an inspection tag
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 machine room fire extinguisher does not have inspection tag
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.11.1 Perform monthly fire service test and post test log in the machine room