ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.11.1
|
|
|
Perform monthly fire service test and post test log in the machine room
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(j)
|
|
|
machine room fire extinguisher does not have an inspection tag
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(j)
|
|
|
machine room fire extinguisher did not have an inspection tag
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
machine room fire extinguisher does not have an inspection tag, have the extinguisher inspected and tagged annually
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
machine room fire extinguisher does not have inspection tag
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.20 - Governor rope
|
8.11.2.1.3(z)
|
x
|
|
Governor rope is rouged and needs to be replaced. 8.6.3.4
|
1/22/2025
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
machine room state operating certificate is from 2019, update with new copy when received from the state annualy
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate on display in the elevator machine room expired in 2019, update annually with current certificate when received from the state
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the copy of the state operating certificate posted in the machine room is to be updated annually
|
|