Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.11.3.1.1(e) No No Must Make Car emergency light operable. 10/13/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Must make Emergency Phone Operable. 8.6.4.15 (Currently calling an inactive no. ) 10/1/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Must make Emegency phone operable. 8.6.4.15 10/13/2025
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 1001.2(b)(8) No No 2.8 power cables feeding controller (inside controller bare wires showing-covering is breaking down-wiring needs replaced) 3/30/2021
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 201 Yes No Car exceeds max. speed for spring buffers (car currently running 275 f.p.m.) 201.1 12/14/2020
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 201 Yes No 201.1 spring buffers are not to be used if elevator exceeds 200 frt per min (elevator tacked at 275' per min) 9/6/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f Yes No Must make Door open and Door close buttons operable. for proper Fire service phase II operation. 211.7 10/1/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.3a(8) Visual and audible signal Yes No Must make both Audible and Visual Signals operable on Fire service activation. 211.3a(8) 10/1/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f Yes No Must Make Door Open and Door Close Buttons Operable. For proper Fire Service Phase II operation 211.7 10/13/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.3a(8) Visual and audible signal Yes No Must make Both Audible and Visual signals operable upon activation of fire service. 211.3a(8) 10/13/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f Yes No Must Make Door Open and Door Close Buttons Operable. For proper Fire Service Phase II operation 211.7
conversion conversion n/a No No springs are not to be used if car exceeds 200 feet/min elevator needs to be slowed down and governor recalubrated 3/30/2021