Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.11.3.1.1(e) Must Make Car emergency light operable.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make Emegency phone operable. 8.6.4.15
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Must Make Door Open and Door Close Buttons Operable. For proper Fire Service Phase II operation 211.7
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.3a(8) Visual and audible signal x Must make Both Audible and Visual signals operable upon activation of fire service. 211.3a(8)
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 201 x 201.1 spring buffers are not to be used if elevator exceeds 200 frt per min (elevator tacked at 275' per min) 9/6/2019
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 201 x Car exceeds max. speed for spring buffers (car currently running 275 f.p.m.) 201.1 12/14/2020
conversion conversion n/a springs are not to be used if car exceeds 200 feet/min elevator needs to be slowed down and governor recalubrated 3/30/2021
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 1001.2(b)(8) 2.8 power cables feeding controller (inside controller bare wires showing-covering is breaking down-wiring needs replaced) 3/30/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make Emergency Phone Operable. 8.6.4.15 (Currently calling an inactive no. ) 10/1/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Must make Door open and Door close buttons operable. for proper Fire service phase II operation. 211.7 10/1/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.3a(8) Visual and audible signal x Must make both Audible and Visual Signals operable on Fire service activation. 211.3a(8) 10/1/2024