Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6 7/27/2022
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. 5/17/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. 7/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.2.7 x Emergency Power fails to bring elevator to a floor when power is removed 7/25/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Need to test the operation of auxiliary lowering. Indicates a drained battery
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit light does not illuminate