ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
The in-car emergency light shall be operational.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an overspeed valve. Based on the installation date the overspeed valve shall be tested with rated load on or before the next annual inspection.
|
1/19/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
11/17/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection)
|
x
|
|
Phase 1 fire hat damaged/broken, leaving open hole in hall station.
|
7/26/2024
|