Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean up the pit and remove all the black mold from the pit walls. 9/12/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a curent state operating certificate in the machine room 9/7/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room. 7/2/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.1 Provide a clear, 36", means of egress to the machine room at all times. 7/2/2020
conversion conversion n/a Provide a complete set of keys to all phases of the elevator operation. 8/15/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1.1.1 Means of Communication (Red Tag) Re program the emergency phone to someone who can take appropriate action in case of emergency. 7/1/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.1 Removce all stored material and equipment from the access pathway to the elevator machine room, You must maintain a minimum of 36" clear. 8/15/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.2.2 Remove all the stored equipment from in front of the elevator machine room door. You must maintain a clear pathway to the equipment. 9/12/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 REpair or replace the machine room door as it will not self close or self lock. 4/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair the emergency as you cannot understand anything the person on the other end is saying as there is so much static on the line. 7/13/2022
conversion conversion n/a Repair the emergency phone as there is no dial tone 8/15/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Replace the drywall in the machine room back to the original 1 hour rated assembly. 9/12/2022