ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean up the pit and remove all the black mold from the pit walls.
|
9/12/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Obtain and display a curent state operating certificate in the machine room
|
9/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Obtain and display a current state operating certificate in the machine room.
|
7/2/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.1
|
|
|
Provide a clear, 36", means of egress to the machine room at all times.
|
7/2/2020
|
conversion
|
conversion
|
n/a
|
|
|
Provide a complete set of keys to all phases of the elevator operation.
|
8/15/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.1 Means of Communication (Red Tag)
|
|
|
Re program the emergency phone to someone who can take appropriate action in case of emergency.
|
7/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.1
|
|
|
Removce all stored material and equipment from the access pathway to the elevator machine room, You must maintain a minimum of 36" clear.
|
8/15/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.2.2
|
|
|
Remove all the stored equipment from in front of the elevator machine room door. You must maintain a clear pathway to the equipment.
|
9/12/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
REpair or replace the machine room door as it will not self close or self lock.
|
4/26/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair the emergency as you cannot understand anything the person on the other end is saying as there is so much static on the line.
|
7/13/2022
|
conversion
|
conversion
|
n/a
|
|
|
Repair the emergency phone as there is no dial tone
|
8/15/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Replace the drywall in the machine room back to the original 1 hour rated assembly.
|
9/12/2022
|