Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display current state operating certificate. 3/26/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Door open button located in the car does not work. 3/26/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No In car emergency light shall work. 3/26/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency bell shall work. 7/11/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No In car emergency telephone shall work. 7/11/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 No No The car top emergency exit shall be securely attached when in both the open and closed positions. 10/22/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams No No Up-to-date wiring diagrams shall be located in the machine room. 10/22/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of Section A17.1 - 2016 - 8.6 10/22/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 6/30/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 6/30/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 7/21/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1, with identification of the person(s) that performed the operation and the date shall be available on site. Note: the last test on the log was from 2020. 7/21/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. Note: The MO certificate in the machine room expired in 2002. 7/21/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.7 Record of Oil Usage No No A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. The written record shall be kept in the machine room. 7/21/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No The in car stop switch shall be rendered inoperative on phase one fire service. 5/31/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall work with and without main power, and give proper location. 6/7/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No The in-car stop switch shall be rendered inoperative on phase one fire service. (2nd Notice) 6/7/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Cab lighting circuit tied to machine room lights and lobby lights. Take corrective action as needed. 6/24/2026