Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - n/a n/a Water in pit needs to be removed 12/26/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.6 - Governor-rope tension devices 8.11.2.1.5(g) Governor tension sheave shall be replaced. 1" rod holding sheave is rusted out. 12/26/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 8.11.2.1.5(c) Check integrity of pit buffers. 12/26/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 Machine room door shall be self closing and locking, and steps leading up to room shall be attached. 12/26/2019
conversion conversion n/a Remove standing water from the elevator pit 12/31/2018
conversion conversion conversion - reinspect x Repair inoperative emergency phone 8/9/2018
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean of dirt and water. 12/31/2018
MO Minimum : Elevators (I) - Pits (I)1 Tail sheave needs to be replaced due to water damage. 12/31/2018
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self closing and self locking. 12/31/2018
MO Minimum : Elevators (N) - Guide Rails (N)2 Check integrity of all rail bottoms (under water and large amounts of rust flaking off). 5.13 12/26/2019
MO Minimum : Elevators (H) - Machine Rooms (H)1 Steps leading up to room shall be attached. 12/25/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking. 12/25/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door needs repair, door hinges pulled from frame and door. 12/25/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete - Governor must be tested for electrical and jaw speeds. Re-inspection required 12/2/2022