ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
2.7.1.1
|
|
|
Hole in machine room wall boarded up with plywood, not fire-rated.
|
9/8/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
2.7.1.1
|
|
|
Machine room enclosure must maintain fire rating. Voids in wall during building vertical expansion construction.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection)
|
x
|
|
In-car visual FS signal not flashing when machine room initiating devices (smokes) activated.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
Emergency Power is existing but was not tested.
|
3/7/2020
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
Emergency power is existing but was not tested.
|
1/19/2023
|