Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency Power is existing but was not tested. 3/7/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency power is existing but was not tested. 1/19/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 Hole in machine room wall boarded up with plywood, not fire-rated. 9/8/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection) x In-car visual FS signal not flashing when machine room initiating devices (smokes) activated.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 Machine room enclosure must maintain fire rating. Voids in wall during building vertical expansion construction.