Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits clean up standing oil in pit 1/10/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting replace burnt out cab ceiling light bulb 3/10/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log post a monthly fire service test log in the machine room and fill it out monthly 3/10/2021
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.11.3.1.5(c) replace the packings on both jacks, the pit bucket overflows between visits 3/10/2021
MO Minimum : Elevators (I) - Pits (I)1 provide a means to prevent ground water from collecting in the pit 3/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.) 12/2/2022
MO Minimum : Elevators (I) - Pits (I)1 I(1)/106.1 Pit shall be kept dry. Remove rust from pit equipment , repaint, investigate/repair water leak. 12/2/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Provide operational telephone inside elevator cab 11/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x CAR DOOR RESTRICTOR SHALL WORK AT ALL FLOORS. 12/2/2022