ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
x
|
|
Fire gibs are missing from the hoistway doors.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
|
conversion
|
conversion
|
n/a
|
|
|
Emergency light shall work.
|
1/15/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.2.1.1(e) Car Lighting
|
|
|
Car emergency lighting shall work.
|
1/15/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP shall be in place as specified in A17.1 2016 - 8.6.1.2.2 and 8.6.1.4
|
2/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
2/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.40 - Maintenance Records
|
2.26.1.5 Inspection Operation With Open Door Circuits.
|
|
|
2.7.6.5.2 - Hoistway/Car door bypass shall be operational.
|
2/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.3
|
x
|
|
2.24.8.4 - The means for manual release of the brakes shall be operational.
|
3/24/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.4.10 Emegency Operation and Signaling Devices
|
x
|
|
Counterweight displacement operation shall be functional.
|
3/24/2021
|