Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)16 Install covers on 4x4 junction boxes located on hoistway wall. 9/16/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) x ADJUST DOOR RESTRICTOR SO IT WORKS 7/8/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 REDUCE THE CLOSING FORCE TO <30 LBS 9/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Cylinder drain lines need to removed from tank. Cylinder drain lines need to drain into seperate pit containers that are covered and no more than 5 gallon capacity. 3/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation Test and log firefighter operation monthly 9/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Cylinder drain lines run back to storage tank. Remove from storage tank and install in pit collection containers 9/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Cylinder drain lines shall be ran to pit collection container and not the hydraulic storage tank in the machine roo.. 9/16/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not illuminate. 7/31/2018
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not illuminate. Need to provide pit lighting. 3/23/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not illuminate. No power at light fixture. Circuit breaker or wiring issue. 9/16/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not illuminate. No electrical power at light fixture. Need to provide power to pit light fixture. 9/16/2025
MO Minimum : Elevators (I) - Pits (I)1 CLEAN OIL FROM PIT FLOOR AND REPAIR LEAK 9/16/2025
MO Minimum : Elevators (I) - Pits (I)8 INSTALL SUMP COVER 9/16/2025
MO Minimum : Elevators (I) - Pits (I)8 REPLACE SUMP PUMP COVER ( IT IS IN THE PIT) 9/16/2025
MO Minimum : Elevators (I) - Pits (I)1 REMOVE STANDING OIL FROM PIT 9/16/2025