MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
EMERGENCY PHONE NOT WORKING
|
7/8/2025
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
REPAIR NON-WORKING IN CAR EMERGENCY PHONE
|
8/20/2026
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
IN CAR EMERGENCY PHONE IS NOT WORKING
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
Yes
|
No
|
Emergency light does not operate.
|
1/19/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.11.1 Firefighters' Emergency Operation & Documentation
|
No
|
No
|
Teat and log firefighter operation monthly
|
9/16/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
No
|
No
|
Cylinder drain line runs back to storage tank. Remove from tank and install into pit collection container
|
9/16/2025
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
No
|
No
|
REPLACE MISSING ELECTRICAL DUCT COVER IN MACHINE ROOM
|
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
REMOVE OIL SOAKED PIG MATS AND CLEAN PIT
|
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
Pits need to be kept dry. Sump pump ntot working. Pit has 2 inches of standing water.
|
7/31/2018
|