Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power and fire service need to be tested.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency light does not work.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit is dirty. Clean the pit.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x In 2023 this elevator inspection was stopped due to a mechanical failure. Almost all of the annual inspection and the complete category 5 test still needed to be completed. The annual was completed 5/28/24 except for fire service and emergency power testing but the category 5 test has not been completed to date. A category 5 test need to be performed and witnessed in its entirety.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.11.2.2.3 x Governor will not electrically set or reset. Governor shall be repaired and tested. 5/29/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.1.4(l) x x Emergency fire service shall be tested. 5/29/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 x 2.4.3 - Provide counterweight runby sign in the pit. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Automatic return to the fire recall floor after coming off Phase 2 fire service does not work and shall be repaired. Violation corrected on 9/21/2020 and scheduled for re-inspection on 10/5/2020. 10/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) Provide missing hoistway door interlock cover at 1st floor. 11/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.40 - Maintenance Records 2.26.1.4 Inspection Operation Provide MCP. 11/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) Governor will not electrically set or reset. Governor shall be repaired and tested. (Violation not cleared from previous annual inspection) 11/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) Clean the car top. 11/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) Provide numbering on car top. 11/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Clean the pit. 11/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) First floor interlock cover is missing and shall be replaced. 11/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 3/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.20 x Car went down during the inspection. Two cables slipped out of the under sling. 5/28/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x The elevator went down during the annual inspection and category 5 test. The following testing items still need to be completed: 1. Door pressure., 2. Inspection of top of car., 3. Inspection of pit., 4. Fire service., 5. Emergency power test., 6. Complete entire category 5 test. 5/28/2024