Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Clean up the oil in the pit. 3/2/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) Have the fire extinguisher re-certified. 3/2/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 Machine room ventilation system is not functioning correctly, provided working AC unit 2/27/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room 3/2/2020
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept free of dirt and rubbish 2/27/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Provide operational machine room ventilation , currently over 115 degrees
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits remove dirt and rubbish from pit floor
MO Minimum : Elevators (I) - Pits (I)1 Remove dirt and rubbish from pit floor 3/24/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) REpair or add more AC to the machine room as the manufacturer requires it to be maintained at 1 to 40 degrees centigrade. It is above 120 degrees today and it is 18 degrees outside. 3/2/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Reprogram the emergency phone. The old monitoring co has disccontinued your service. 1/2/2020