Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6 7/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.2.7 Yes No Emergency Power batteries are damaged. Emergency Power inoperable 7/25/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 8.11.2.1.1(c) No No Door Close button on Car Operating Panel is inoperable 7/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.24.8.4 Means for Manual Release No No Emergency Brake Release is inoperable 7/27/2022
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(t) Yes No 2.24.8.4 Emergency Brake Release is inoperable. Indicates a drained battery 2/22/2024
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake Yes No Need to perform unintended movement test. The method to perform the test was not working 2/22/2024
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 No No Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. 5/17/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) No No Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail 7/27/2022