MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
mach room lock dosnt latch door closed
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.9 - Floor and emergency identification numbering
|
2.29.2
|
|
|
emg hall door identfication not on hall doors
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
no MCP on site
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emg. phone not working
|
6/19/2020
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.5.14.3(f)
|
x
|
|
battery lowering not working
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Need a non GFCI outlet in pit for sump pump
|
2/26/2019
|