Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 3/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 8.11.2.1.1(c) Make door hold button operational. 3/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. 2.11.11.8
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.6 - Governor-rope tension devices 8.11.2.1.5(g) When the tension sheave switch is tripped the elevator stops in flight. When the tension sheave switch is tripped the elevator should complete its run then remain inoperative until the switch is reset. 2.18.7.2
conversion conversion n/a Need copy of current state operating certificate in machine room. 3/4/2020
conversion conversion n/a Replace broken "Door Hold" button. 3/4/2020