Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emg phone didnt call out
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emg. power couldnt be tested at time of insp. 1/24/2022
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) x runby less than 6 ins. need to shorten ropes spring buffers 1/24/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.10 - Compensating chains, ropes, and sheaves 8.11.2.1.5(h) comp chains rubbing pit floor 1/24/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation procedures for insp an testing not on site 1/24/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.3.5 x Emergency power not tested at time of inspection. 1/9/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x couldnt test emg power at time of insp 4/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) x rope data tag says ropes are suppose to be 13mm but cables are 1/2 in. excessive metal flaking from sheaves 4/15/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate current cirt not displayed 9/10/2024