A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emg. power couldnt be tested at time of insp.
|
1/24/2022
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11 Runby (Re-Inspect)
|
x
|
|
runby less than 6 ins. need to shorten ropes spring buffers
|
1/24/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
procedures for insp an testing not on site
|
1/24/2022
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
couldnt test emg power at time of insp
|
4/15/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emg phone didnt call out
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection)
|
x
|
|
rope data tag says ropes are suppose to be 13mm but cables are 1/2 in. excessive metal flaking from sheaves
|
4/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.3.5
|
x
|
|
Emergency power not tested at time of inspection.
|
1/9/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.10 - Compensating chains, ropes, and sheaves
|
8.11.2.1.5(h)
|
|
|
comp chains rubbing pit floor
|
1/24/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
current cirt not displayed
|
9/10/2024
|