Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the state operating certificate shall be displayed in the machine room
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Car safety not tested. Provide car to run at contract speed. Cat 5 safety test required. Record slide.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Car speed is rated at 200 fpm. Up full load =70fpm, down=150. Provide car to run at contract speed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Car traveling at 16% of contract speed. Determine cause and perform full load safety test for proper slide.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 3/2/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Expired
conversion conversion n/a No No Per Larry Watson, he gave Kone two weeks to complete repairs.
conversion conversion n/a No No Per Larry Watson, he gave Kone two weeks to complete repairs.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Provide machine room door to be self locking.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No Provide MCP
conversion conversion n/a No No Test not complete. Car failed 125% brake test. Also, car was not running contract speed.
conversion conversion n/a No No Test not complete. Car failed 125% brake test. Also, car was not running contract speed.