| ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits |  |  | The pit light shall work. | 10/28/2019 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits |  |  | Remove fluids from the pit. | 10/28/2019 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 5.11 - Plunger and Cylinder | 3.18 |  |  | The left hydraulic jack packing is worn and leaking. Repair or replace as needed. | 10/29/2019 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | Display current state operating certificate. | 10/29/2019 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 1.17 - Standby power operation | 2.27.2 | x |  | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/28/2023 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 1.17 - Standby power operation | 2.27.2 | x |  | Emergency power must be tested annually. (2nd Notice) | 9/9/2024 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | x |  | Battery lowering unit has been removed and shall be replaced or a variance applied for. See MO Memorandum 016 for more details. | 5/7/2025 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 1.17 - Standby power operation | 2.27.2 | x |  | Emergency power operation shall be tested. | 5/7/2025 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/14/2025 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 2.6 - Ventilation | 2.7.5.2 |  |  | The ventilation fan is not working. Must repair or replace. | 10/14/2025 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 1.17 - Standby power operation | 2.27.2 | x |  | Unit recalled on battery lowering but did not switch to generator power. Elevators equipped to operate on generator power shall be tested annually. | 10/14/2025 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/14/2025 | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing |  |  | This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 10/14/2025 |