MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The bottom landing call button is located under the elevator when it's at the top landing. It shall be re-located within sight of the elevator, but out of the path of the elevator as it's moving down. Note (1): This elevator was granted a variance in the past, but the specifics of that variance were not provided to the inspector or available to the public at the time of inspection. Note (2): The MO AHJ has indicated they will be looking into this variance and the installation to ensure the unit is compliant and safe. Note (3): It is recommended that the bottom landing call station be changed to keyed operation to further ensure usage by authorized personnel only.
|
11/5/2024
|