MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)5
|
|
|
Properly secure cab lights to ceiling.
|
|
conversion
|
conversion
|
n/a
|
|
|
Replace electrical conduit on side of car
|
7/25/2018
|
conversion
|
conversion
|
n/a
|
|
|
Cover junction box on car top
|
7/25/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Fire extinguisher needs to be serviced.
|
12/11/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022)
|
3/7/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Provide a current tested fire extinguisher in the elevator machine room.
|
3/8/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing and self-locking.
|
3/8/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
A permanent lighting fixture shall be provided in all pits to provide illumination of not less then 5 ftc at the pit floor.
|
3/8/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide a code compliant MCP including onsite documents.
|
3/8/2022
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)4
|
x
|
x
|
The movement of the safety drum rope, starting from a fully retracted position, must not exceed 42 inches (it pulled out approximately 120 inches) before the safety shoes contact the rail. Elevator Red Tagged.
|
10/10/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Water and oil shall not be allowed to accumulate on the pit floors. Note: The pit floor is covered with several inches of water.
|
3/14/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
All electrical wiring in the hoistway shall be enclosed in metal conduit, flexible conduit, metal raceway, or be in compliance with NFPA70. Note: There are bare wires running throughout the hoistway.
|
3/14/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
The missing junction box covers in the hoistway shall be replaced.
|
3/14/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)12
|
|
|
The penetrations in the hoistway shall be sealed with approved materials.
|
3/14/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The fluorescent pit light shall be operational and permanently wired. Note: The fixture is currently attached to a cord which runs through a hole in the hoistway wall and is plugged into an extension cord.
|
3/14/2023
|